| Quick Help
The
object name, value, and status are shown for a list of objects starting
with the number entered at the top of the page. Click Prev/Next to
scroll through the list. Click on the object number in the first column
to change name or out-of-service status. The
source of data for a Multistate Input object will typically be
reading from some other BACnet or Modbus device. Click on the
object number in the first column for more detail including the link to
any client map providing data to this object. Out
of Service means polling for data will stop. While out of service, the
present value may be written by the BACnet client. Data may be forced
via this web page at any time, but will be overwritten by the next
mapped client update unless the object is out of service. Reliability codes may be any of the following: Modbus client/master, no response from slave (64) Modbus client/master, crc error (65) Modbus exception, illegal function code (66) Modbus exception, illegal data address (67) Modbus exception, illegal data value (68) Modbus exception, code+65, rarely used (69..79) Local device, configuration property fault (80) Faulty Modbus packet(81) BACnet client, device timeout (82) BACnet client, error returned by server (83)
Status flags A,B,C,D indicate the following, 0 meaning not true, 1 meaning true: A = in alarm B = fault C = overridden D = out of service | | |