The following properties are found in the Analog, Binary, and Multi-state types of Input, Output, and Value objects. Some properties apply only to certain object types as noted where applicable.
Property | Encoding |
Object_Identifier (75) | BACnetObjectIdentifier |
Object_Name (77) (W) | CharacterString “Analog Input n” |
Object_Description (28) (W) | Character String Same as Object_Name, is only alias for Object_Name |
Object_Type (79) | BACnetObjectType ENUMERATED: analog-input (0) analog-output (1) analog-value (2) binary-input (3) binary-output (4) binary-value (5) device (8) multi-state-input (13) multi-state-output (14) multi-state-value (19) |
Present_Value (85) (W) |
REAL (analog objects) |
Status_Flags (111) | BACnetStatusFlags BIT STRING: fault(1), out-of-service(3) |
Event_State (36) | BACnetEventState ENUMERATED: normal(0), fault(1) |
Reliability (103) | BACnetReliability ENUMERATED: normal(0) Vendor specific: no response (64) crc error (65) exception, illegal function code (66) exception, illegal data address (67) exception, illegal data value (68) exception, code+65, rarely used (69..79) configuration property fault (80) exception, code not recognized (81) BACnet client read/write timeout (82) BACnet client received error response from slave (83) |
Out_Of_Service (81) (W) | BOOLEAN |
COV_Increment (22) (W) | REAL (analog objects only) |
COV_Period (180) (W) | Unsigned |
Priority_Array (87) | BACnetPriorityArray (commandable objects only) SEQUENCE SIZE (16) OF BACnetPriorityValue REAL (each element, analog output objects) ENUMERATED (each element, binary output objects) Unsigned (each element, multi-state output objects) |
Relinquish_Default (104) (W) |
REAL (analog objects) |
Polarity (84) | BACnetPolarity (binary objects only) ENUMERATED: normal(0) |
Number_Of_States (74) | Unsigned (multi-state objects only) |
Units (117) | BACnetEngineeringUnits (analog objects only) |
Active_Text (4) | CharacterString (binary objects only) |
Inactive_Text (46) | CharacterString (binary objects only) |
State_Text (110) | CharacterString (multistate objects only) |
Vendor Specific Object Properties: | |
Object_Map_Usage (801) (W) | BIT STRING: (0) object is mapped to Modbus (1) object included in packed group (2) object included in mixed type packed group (3) reserved (4) set default on power-up (5) set default on comm. fail (6) read periodic (7) write periodic (8) write on delta (9) enable max quiet (10) object is mapped to BACnet |
Poll_Period (802) (W) | Unsigned Modbus poll/update time in seconds |
Note: Properties 803 through 808 can only be written when bit 0 of the Object_Map_Usage bit string is set. Properties 819 through 826 can only be written when bit 10 of the Object_Map_Usage bit string is set. Bits 0 and 10 of the Object_Map_Usage bit string cannot both be set at the same time (doing so will cause unpredictable behavior). | |
Register_Number (803) (W) | Unsigned Modbus register number 1..65535 |
Register_Type (804) (W) |
ENUMERATED: |
Register_Format (805) (W) |
ENUMERATED: |
Modbus_Slave_ID (806) (W) |
ENUMERATED: |
Register_Bit_Mask (807) (W) | Unsigned |
Register_Bit_Fill (808) (W) | Unsigned |
Slope (809) (W) |
REAL |
Intercept (810) (W) | REAL |
Default_Value (811) (W) | REAL (analog objects) ENUMERATED (binary objects) Unsigned (multi-state objects) |
Max_Quiet_Time (812) (W) | Unsigned |
BACnet_Slave_Timeout (813) (W) | Unsigned |
Max_Read_Fail_Count (814) (W) | Unsigned |
Send_On_Delta (815) (W) | REAL (analog objects only) |
Initial_COV_Increment (816) (W) | REAL (analog objects only) |
Initial_COV_Period (817) (W) | Unsigned |
Initial_Relinquish_Default (818) (W) | REAL (analog objects) ENUMERATED (binary objects) Unsigned (multi-state objects) |
BACnet_Slave_Device (819) (W) | Unsigned |
Slave_Object_Type (820) (W) | ENUMERATED |
Slave_Object_Instance (821) (W) | Unsigned |
Slave_Index (822) (W) | Unsigned (value is index+1, 0=no index) |
Slave_Priority (823) (W) | ENUMERATED (1..16) |
Slave _Property_Type (824) (W) | ENUMERATED (see BACnet protocol specification for type codes) |
Slave_Data_Encoding (825) (W) |
ENUMERATED |
Slave _Bit_Position (826) (W) | ENUMERATED |
Error_Class (830) | Unsigned |
Error_Code (831) | Unsigned |
Config_Write_Command (832) (W) | ENUMERATED (1) write config to EEPROM |
The following properties are found in the Device object of the BB3-3101. In addition to standard Device properties, configuration properties that apply at a system level to the whole device are included here.
Property | Encoding |
Object_Identifier (75) | BACnetObjectIdentifier |
Object_Name (77) | CharacterString |
Object_Type (79) | BACnetObjectType ENUMERATED: device (8) |
System_Status (112) | BACnetDeviceStatus |
Vendor_Name (121) | CharacterString |
Vendor_Identifier (120) |
Unsigned16 |
Model_Name (70) | CharacterString |
Fimrware_Revision (44) | CharacterString |
Application_Software_Version (12) | CharacterString |
Protocol_Version (98) | Unsigned |
Protocol_Revision (139) | Unsigned |
Protocol_Services_Supported (97) | BACnetServicesSupported |
Protocol_Object_Types_Supported (96) | BACnetObjectTypesSupported |
Object_List (76) | BACnetARRAY[N] of BACnetObjectIdentifier |
Max_APDU_Length_Accepted (62) | Unsigned |
Segmentation_Supported (107) | BACnetSegmentation |
APDU_Timeout (11) | Unsigned |
Number_Of_APDU_Retries (73) | Unsigned |
Device_Address_Binding (30) | List of BACnetAddressBinding |
Database_Revision (155) | Unsigned |
Description (28) | CharacterString |
Location (58) | CharacterString |
Max_Segments_Accepted (167) | Unsigned |
APDU_Segment_Timeout (10) | Unsigned |
Active_COV_Subscriptions (152) | BACnetLIST of BACnetCOVSubscription |
Last_Restart_Reason (196) | BACnetRestartReason |
Max_Master (64) | Unsigned (0..127) |
Max_Info_Frames (63) | Unsigned |
Restart_Notification_Recipients (202) | BACnetLIST of BACnetRecipient |
Time_Of_Device_Restart (203) | BACnetTimeStamp |
Vendor Specific Object Properties: | |
RTU_Port_Baud_Rate (851) (W) |
ENUMERATED: |
RTU_Character_Forma t(852) (W) |
BITSTRING: |
RTU_Slave_Timeout (853) (W) |
Unsigned |
RTU_Slave_Address (854) (W) |
ENUMERATED |
RTU_Pre_Delay (855) (W) | Unsigned |
Max_State_Per_Multistate (856) (W) | Unsigned |
RTU_Message_Count (861) (W*) |
Unsigned |
RTU_Exception_Count (862) (W*) |
Unsigned |
RTU_Bad_CRC_Count (863) (W*) |
Unsigned |
RTU_No_Response_Count (864) (W*) |
Unsigned |
W* -- Registers are “writeable” for purposes of resetting error counts. Writing any value will reset count to zero. Total message count will stop at 65535. Error counts will stop at 255. Counting will resume when reset to zero. | |
RTU_Error_Scan (865) (W) |
Unsigned |
RTU_Raw_Command (871) (W) |
OCTET_STRING |
MSTP_Port_Baud_Rate (1201) (W) |
ENUMERATED: |
MSTP_Station_ID (1202) (W) | Unsigned |
Enable_Auto_Reset (1203) (W) |
BOOLEAN |
Reinit_Password (1205) (WO) |
CharacterString |
Password_Unlock (1206) (W) |
Unsigned |
Device_Allocation (1251) (W) |
Unsigned NOTE: After writing all 10 object allocation counts, a WARMSTART must be issued. All object maps will be cleared. |