						 The
 object name, units, value, and status are shown for the object number 
entered at the top of the page. Click Prev/Next to scroll through the 
list. Click Refresh to update the page, or Update to accept changes. The
 object name and description may be changed here. BACnet units may be 
selected. Initial COV increment may be entered. When any of these are 
changed, be sure to save the updated configuration by clicking Save on 
the Config File page under System Setup.  The
 object may be set Out of Service by checking that box and clicking 
Update. The present value may be changed by entering a value, checking 
Force, and clicking Update.  Analog
 Value objects may be both a source and destination for some other 
BACnet device. The source of data for the Value object will be 
reading from a remote device when associated with a Read Map. The 
destination of data for the Value object will be writing to a remote 
device when associated with a Write Map. If a remote device is mapped, 
the device links are displayed above. You may click on either link to 
view the respective mapping. The
 Value object may be simultaneously associated with both Read and Write 
maps pointing to the same remote device object. When this Value object 
receives new data (from any source), this data will be written to 
the mapped remote device before any subsequent read from the same 
device. Thus the Value data is not discarded by the read operation 
before the new data can be written.  Out
 of Service means polling of the remote device will stop. While out of 
service, the present value may be written by an external BACnet client 
but it will not be written to any mapped remote device. Data may be 
forced via this web page at any time, but will be overwritten by the 
next read from a remote device unless the object is out of service.  Reliability codes indicate errors as itemized on the tabular object list.
  Status flags A,B,C,D indicate the following, 0 meaning not true, 1 meaning true: A = in alarm B = fault C = overridden D = out of service  Device
 link will indicate RTU, TCP, or BIP, followed by R for read or W for 
write, and a number which is the map number in the table of read or 
write maps for mapping to this BACnet object. The designation R means 
read from a remote device, and W means write to a remote device. Check 'Deconfigure' and click Update to erase configuration for this object.  |