| |
| Quick Help
The
object name, units, value, and status are shown for a list of objects
starting with the number entered at the top of the page. Click Prev/Next
to scroll through the list. Click on the object number in the first
column to change name, units, COV, and out-of-service state. The
destination of data for an Analog Output object will typically be
some other BACnet or Modbus device. Click on the object number in
the first column for more detail including the link to any client map
receiving data from this object. The
Analog Output object is commandable, meaning the BACnet client
must write both a value and a priority level for that value. The highest
level value will be the one written to the remote device (if mapped).
If all values are relinquished, the relinquish default value will be
written to the remote device. Out
of service means the mapped remote device will not be written to.
Values written by the BACnet client will be retained, but only
applied when this object is placed back in service. At that time, the
highest priority value will be written to the remote device. Reliability codes may be any of the following: Modbus client/master, no response from slave (64) Modbus client/master, crc error (65) Modbus exception, illegal function code (66) Modbus exception, illegal data address (67) Modbus exception, illegal data value (68) Modbus exception, code+65, rarely used (69..79) Local device, configuration property fault (80) Faulty Modbus packet(81) BACnet client, device timeout (82) BACnet client, error returned by server (83) Host update timeout (84)
Status flags A,B,C,D indicate the following, 0 meaning not true, 1 meaning true: A = in alarm B = fault C = overridden D = out of service | | |