| Quick Help
						 Write
 local registers out to remote registers. This page creates a map entry 
that writes data to one or more remote Modbus/TCP servers from data 
contained here. Click on map number to see more detail and insert/delete
 maps. Map
 number simply tells you where you're at on the list of register maps. 
Click "next" and "prev" to scroll through the list. To advance directly 
to a specific map, enter the desired number in the "Showing" box, 
then click Update.  Maps
 entered on this page only write data to remote devices. Go to the 
Client Read Map to read data from those devices. The full parameter set 
is different for read versus write. An
 abbreviated version of a list of maps is shown on this page. Any of the
 parameters shown may be changed here and registered by clicking the 
Update button. To view and/or modify the complete set of parameters, 
click on the map number in the left most column.  For
 each remote register to be written, enter the register type, format, 
number, and location (device). The names in the device list are defined 
in the Devices page. If register format is CHAR, you need to click on 
the map number and set the string size on the expanded view of the map 
map. For coils or discrete inputs, use INT-16 or UINT-16 for register 
format - in this case, format only affects formatting of local register 
data. Selecting
 "none" for remote type effectively deletes the map even though it will 
still appear in the list until deleted. Unused maps at the end of the 
list will always show none as the type.   |