| Quick Help
						 Map
 number simply tells you where you're at on the list of register maps. 
Click "next" and "prev" to scroll through the list. To advance directly 
to a specific map, enter the desired number in the "Map #" box, 
then click Update.  For
 each remote register to be read, enter the register type, format, 
number, and slave address or unit number. Size is only applicable when 
format is Character String, and specifies the number of characters that 
are to be packed 2 per register. Any size greater than 2 characters 
implies a multiple register read from the Modbus slave. For coils or 
discrete inputs, use INT-16 or UINT-16 for register format - in this 
case, format only affects formatting of local data. When
 the remote register is read, data may be manipulated before being 
written to the local object. If a bit mask is entered (in hexadecimal), 
and the remote register type is signed or unsigned (16-bit data), the 
mask will be bit-wise logical AND-ed with the data, and the retained 
bits will be right justified in the result. The result will then be 
multiplied by the scale factor. The offset is then added and this 
final result is written to the local object number given.  The
 default value will be stored into the local object after the given 
number of read failures if the fail count is non-zero. Setting the count
 to zero will disable the default, and the object will retain the most 
recent value obtained.  The
 periodic poll time determines how often the remote register will be 
read. This number, if nonzero, will override the default poll time given
 in the Devices page for the remote device being read.  You
 have the option of enabling this map only when a selected object 
contains a given value. Any local object may be used as the index 
object. As the name implies, you could have the same local object 
contain different values based on different maps as indexed by the index
 object.  Delete
 will remove the map number shown in the "Map #" box. Insert will 
insert a new map before the map number shown, and is used for placing 
maps between existing mapss. It is not necessary to use Insert to add 
maps to the bottom of the list or to define any map presently having 
zero for a source register or "none" for remote type.  Selecting
 "none" for remote type effectively deletes the map even though it will 
still appear in the list until deleted. Unused maps at the end of the 
list will always show none as the type. If you wish to prevent these 
from being displayed, reduce the number of maps enabled.  The
 number of maps enabled simply limits the scope of map review so that 
you do not have to review a lot of unused maps. If the displayed maps 
are used up and you need more, increase the enabled number.   |