Click on any tab above to log in.
Discrete OutputsDO 1-8Green LED indicators light when respective relay output is "on".
Power &
Processor Activity
ACTGreen LED, on with brief flickers off at a 1-second rate, indicates I/O processor is running.
PWRGreen LED indicates power is present independent of any processor activity. This indicator is on the secondary side of the internal DC/DC converter. If power is present at the input terminals but this LED does not light, there is a hardware fault.
Modbus RTU or
BACnet MS/TP
TXYellow LED flashes each time a packet is sent out on the RS-485 network line.
RXYellow LED flashes each time a packet is successfully received on the RS-485 network. This LED will not flash if unrecognized communication is received.
ERRNormal operation: Red LED flashes any time a request to an external device times out (no response), or the response from the remote device contained an error (such as CRC error).

Bootloader: Upon power-up, the bootloader checks the integrity of the application. If program memory has been corrupted in the co-processor, the red light will remain on with brief flickers off at a 1-second rate, and the green ACT LED will remain off.

Ethernet(link)Yellow LED indicates an Ethernet link is present. This indicator will light if a link is present regardless of processor or network activity. If not lit, check network wiring.
(activity)Green LED is on solid during portions of the boot-up process, and then flashes briefly when Ethernet network traffic is detected.
I/O ActivityIOGreen LED flickers rapidly indicating communication between the web server and I/O processor.
ACTGreen/Yellow bi-color LED is on solid green most of the time, with rapid brief flickers of yellow and brief flashes off indicating activity within the web server.
Discrete HOA SwitchesThe 8 HOA switches are 3-position switches which may override outputs by driving the relay coils (load is not directly switched). The lower position (A) puts the output in automatic mode under control of the processor. The middle position (O) forces the relay off, and the upper position (H) forces the relay on. The LED directly above the HOA switch indicates the state of that output.
Soft ButtonThe soft button has software defined use if and when noted.