Detailed Product Listing
BABEL BUSTER 485
NETWORK GATEWAY

Babel Buster® 485

LonWorks® to Modbus/RTU Gateway

Translates any Modbus register to any supported LonWorks SNVT variable and vice versa!

• Connect Modbus devices to a LonWorks network
• Connect LonWorks devices to a Modbus network
• Any LonWorks SNVT, any Modbus Register Format






Babel Buster 485 Modbus RTU to LonWorks Gateway

Order code: 00BB485

List:
$498.00
Your price:
$399.00
Log In for
Wholesale

Looking for application specific Modbus to LonWorks gateways? Click here!
Software Options
The standard Babel Buster 485 provides 30 NVOs and 28 NVIs. The -F50 option provides 46 NVOs and 8 NVIs. The -T50 option provides 8 NVOs and 50 NVIs. Select the "T50" option if data is flowing mostly "To Modbus", and "F50" if data is flowing mostly "From Modbus". Select the standard version (no suffix) for a roughly even mix.
You can convert Babel Buster 485 to another version simply by re-commissioning the device in LonMaker, and selecting the "Load Application Image". The optional images and XIF files may be downloaded from the zip file right here.

Babel Buster 485 Images


Babel Buster 485 is a fully configurable universal LonWorks to Modbus RTU gateway. The RTU master is used to make Modbus RS-485 devices accessible on a LonWorks network. The RTU slave is used to make LonWorks devices accessible on a Modbus RS-485 network. The Babel Buster 485 gateway is designed to be economical enough to use multiple gateways, one per device or group of devices, rather than run parallel networks to a larger, more expensive gateway.

An RTU master Babel Buster 485 can poll multiple Modbus slaves, and can be bound to any number of LonWorks devices. An RTU slave Babel Buster 485 responds to a single Modbus slave unit ID, and may be bound to any number of LonWorks devices. LonWorks network variable data is translated to Modbus register data, and vice versa. Modbus polling rates and LonWorks network update rates are fully configurable. Register mapping and network variable types (SNVT) are fully configurable.

The LonMark Certified Babel Buster 485 conforms fully to LonMark version 3.3. The only tool required to configure Babel Buster is LonMaker version 3.

• Universal, fully configurable
• You pick the Modbus register
• You pick the SNVT type
• No extra software or drivers to buy

• LonWorks TP/FT-10 (FTT-10A) to Modbus RS-485 Gateway
• Translate 58 LonWorks variables to Modbus registers
• LonMark Ver. 3.3 Sensor & Actuator Functional Profiles
• Modbus “coils”, input registers, holding registers
• Single or double Modbus registers
• Signed, unsigned, IEEE 754
• All scalar LonMark SNVT types supported
• SNVT_switch & SNVT_state also supported
• SNVT types dynamically assignable via LonMaker
• Modbus registers dynamically mappable via LonMaker
• Modbus registers may be scaled (x10, x0.1, etc.)
• Min/max send time, send on delta configurable per point
• Modbus (master) polling interval configurable per point
• Object override supported on point by point basis
• Bidirectional communication between LonWorks & Modbus
• LonMark certified, version 3.3
• 3150L Neuron® Chip, 48K Flash memory, 10K RAM
• TP/FT-10 (FTT-10A) transceiver
• Powered by 10-30VDC or 12-24VAC 50/60 Hz
• Power Consumption: 0.1A @ 24VDC
• DIN rail mounting, 100mm H x 70mm W x 60mm D
• LED indicators for LonWorks & Modbus status
• Pluggable screw terminal blocks
• Operating temperature -40°C to +85°C
• Humidity 5% to 90%
• FCC Class B, CE Mark

Connect LonWorks I/O to Modbus I/O with Babel Buster.
Click image above for preview of FREE configuration and diagnostic tool for Babel Buster. Tool requires Echelon OpenLDV and a supported LonWorks network interface such as i.Lon 100, PCLTA-21, PCC-10, or U10.

Echelon USB LonWorks Interface for TP/FT-10 is available on our web site as a convenience. You may also purchase this item from Echelon Corp.

Go to Accessories page to order.

If you need to connect one or more Modbus RTU devices to a LonWorks network, you found the right product here!

How do you configure the gateway? If you recognize 40001 as a reference to a holding register, you've got it figured out. Just type it in.

If you need to connect a LonWorks device to a Modbus network, you are getting closer, but the product you really want is the
Babel Buster 485-DS.

How do you map Modbus registers to LonWorks network variables? Click here to see how the configuration tool works for a better idea of how this is done.

Is it a gateway or an object server? Click here for answers.